Basic protection for 4-wire information technology systems with RJ45

Lightning current combination arrester, type 1+2 to DIN EN 61643-11

• For lightning protection equipotential bonding to VDE 0185-305 (IEC 62305)
• Complete unit, pre-mounted and ready for connection in polycarbonate housing (IP66)
• Lightning current arresting capacity 12.5 kA (10/350) per pole and up to 50 kA (10/350) in total

Application: Lightning protection equipotential bonding for buildings of Class III and IV.
If there is a danger of condensation forming through wind, ice, temperature or sunlight, further measures may be necessary!

Connection options

RJ45 S-E100 4-B

Maximum continuous voltage AC

UC

120

Maximum continuous voltage DC

UC

170

Category

 

Type 1+2 / D1+C2

Lightning protection zone LPZ

 

0→2

Number of poles

 

4

Rated current

IL

1

Series resistance per wire

 

Impulse durability wire-wire

 

C2: 3 kV / 1.5 kA (8/20 µs)

Impulse durability wire-earth

 

C2: 3 kV / 1,5 kA (8/20µs)

Impulse discharge current (10/350)

Iimp

0,5

Total discharge current (8/20)

 

8

Total discharge current (10/350)

 

2

Protection level wire-wire

 

Protection level wire-earth

 

Frequency range

 

0 – 463 MHz

Insertion loss

S21

≤3

Temperature range

ϑ

-40-80

Installation type

 

Connector/cable adapter

Connection system

 

RJ45

Protection rating

 

IP40

Shielding connection available

 

Yes

Shield connection

 

Indirect

Earthing via:

 

Connection cable

Testing standard

 

IEC 61643-21