Lightning current and surge arrestor, 3-pole

V 50-B+C/…: Combination arrestor set, lightning and surge arrestor Type 1+2 to DIN EN 61643-11 (B+C to VDE 0675 Part 6).

• For lightning protection equipotential bonding to VDE 0185-305 (IEC 62305)
• Lightning current arresting capacity 12.5 kA (10/350) per pole
• Universally suitable for TN-C systems
• With new Multibase base with multi-connection terminals
• Complete unit, consisting of cover and base, pre-mounted and ready for connection
• arrestor, connectable with dynamic cut-off unit
• With visual function display
• Voltage protection level • Encapsulated, non-extinguishing zinc oxide varistor arrestor for use in distributor housings
• Labelled connections

Application: Equipotential bonding in buildings, even those with external lightning protection of Class III and IV, and in standard distributor housings.

Connection options

V50-B+C 3-280

Nominal voltageUN230
SPD to EN 61643-11Type 1+2
SPD to IEC 61643-11class I+II
Lightning protection zone LPZ0→2
Impulse discharge current (10/350)Iimp12,5
Total discharge current (10/350)Itotal37,5
Nominal discharge current (8/20)In30
Arrestor surge current (8/20) [total]ITotal 8/2090
Maximum discharge current (8/20 μs)Imax50
Voltage protection levelUp
Response timetA
Maximum back-up fuse125
Temperature rangeϑ-40-80
Division unit TE (17.5 mm)3
Protection ratingIP20
Connection cross-section rigid2,5-35
Connection cross-section, multi-wire2,5-35
Connection cross-section, flexible2,5-25